ODRA

ODRA

ODRA compartmentalised switchgear systems are intended for operation in AC 50 Hz distribution networks with rated voltages of up to 36 (40.5) kV.

Switchgear may be executed either in free standing or against wll setup. ODRA switchgears with instrumentation are suitable for operation under normal condition according to PN-EN 62271-200 standard.

The ODRA system of MV compartment switchgear units was awarded the Silver Medal of Polskie Sieci Energetyczne during the Energetab exhibition in Bielsko-Biała, Poland.

Advantages of switchgear ODRA:

  • high safety of operation ensured by:
    • mechanical and electromechanical interlocks, which prevent erroneous switching operations when using the switchgear
    • all mechanical operations with the door closed
    • signaling of voltage presence in the primary circuit
    • constructional solutions protecting from internal arc effects
  • compact overall dimensions,
  • high resistance to corrosion,
  • use of the modern and reliable apparatus
  • easy operation and maintenance with wall setup

Switchgear ODRA were tested at the Institute of Electrotechnics in Warsaw and come with the Certificates No. 0798/NBR/02010, 0819/NBR/2010 and 0611/NBR/09 verifying their rated parameters and admitting them for use at power distribution plants, power stations, industrial plants and other facilities generating, transmitting or using electric energy.

The ODRA switchgear units can be installed in:

  • main supply terminals,
  • pad mounted transformers
  • switchgear solutions for auxiliary consumption.


The ODRA MV switchgear units are:

  • for indoor applications;
  • withdrawable;
  • compartmentalized;
  • in metal enclosures;
  • air insulated;
  • complete with metal partitions;
  • with a single busbar system;
  • provided with modern switching gear solutions.

Technical data of switchgear ODRA

Rated insulation voltagekV1217,52436 (40,5*)
Rated lightning impulse withstand voltage (1,2/50μs)kV75/8595/110125/145170/195
190*
Rated power frequency withstand voltagekV28/32
42/48*
38/4550/6070/80
95*
Rated frequencyHz50
Rated continuous current of busbarsAup to 
3150
up to 
2500
up to 
2000
up to 
1250
Rated short time withstand currentkAup to 
31,5/3s
up to 
25/3s
Rated peak withstand currentkAup to 80up to 63
Withstand for internal arcing faultkA31,5/1s25/1s
Degree of protectionIP 41 / IP 4X
IAC classification (class of resistance to internal arc)AFLR
PM/PI classification (class of partitions)PM
LSC classification (class of compartment accessibility)LSC2B
Weight of a single switchgear cubiclekg550-1200900-1600
Busbar systemsingle
Overall dimensions (width)**mm600 - 1200
Overall dimensions (depth)**mm1250 - 2500
Overall dimensions (height)**mm2150 - 2560

* - required according to ГOCT

** - without external guards, covers, doors

Environmental operating conditions

Switchgear ODRA with installed switchgear are adapted for indoor operation under normal conditions, with the following environmental conditions:

Installation altitude above sea levelto 1000 m
Ambient temperature:peak short-time+40°C
maximum average during the day+35°C
maximum average yearly+20°C
minimum sustained-5°C
Air relative humidity at +40°C:during the start upmax. 80%
during standstill or operationmax. 95%

Certificates

Switchgear ODRA were tested at the Institute of Electrotechnics in Warsaw and come with the Certificates verifying their rated parameters and admitting them for use at power distribution plants, power stations, industrial plants and other facilities generating, transmitting or using electric energy.

Latest catalogue of ODRA MV switchgear system:

Download the catalog card

The website uses cookies

As part of our website, we use cookies to provide you with services at the highest level, including in a manner tailored to individual needs. Using the website without changing the cookie settings means that they will be stored on your end device. You can change your cookie settings at any time. More details in ours "Cookies policy".