ODRA
ODRA compartmentalised switchgear systems are intended for operation in AC 50 Hz distribution networks with rated voltages of up to 36 (40.5) kV.
Switchgear may be executed either in free standing or against wll setup. ODRA switchgears with instrumentation are suitable for operation under normal condition according to PN-EN 62271-200 standard.
The ODRA system of MV compartment switchgear units was awarded the Silver Medal of Polskie Sieci Energetyczne during the Energetab exhibition in Bielsko-Biała, Poland.
Advantages of switchgear ODRA:
- high safety of operation ensured by:
- mechanical and electromechanical interlocks, which prevent erroneous switching operations when using the switchgear
- all mechanical operations with the door closed
- signaling of voltage presence in the primary circuit
- constructional solutions protecting from internal arc effects
- compact overall dimensions,
- high resistance to corrosion,
- use of the modern and reliable apparatus
- easy operation and maintenance with wall setup
Application and features of the system
Switchgear ODRA were tested at the Institute of Electrotechnics in Warsaw and come with the Certificates No. 0798/NBR/02010, 0819/NBR/2010 and 0611/NBR/09 verifying their rated parameters and admitting them for use at power distribution plants, power stations, industrial plants and other facilities generating, transmitting or using electric energy.
The ODRA switchgear units can be installed in:
- main supply terminals,
- pad mounted transformers
- switchgear solutions for auxiliary consumption.
The ODRA MV switchgear units are:
- for indoor applications;
- withdrawable;
- compartmentalized;
- in metal enclosures;
- air insulated;
- complete with metal partitions;
- with a single busbar system;
- provided with modern switching gear solutions.
Technical data and certificates
Technical data of switchgear ODRA
Rated insulation voltage | kV | 12 | 17,5 | 24 | 36 (40,5*) |
---|---|---|---|---|---|
Rated lightning impulse withstand voltage (1,2/50μs) | kV | 75/85 | 95/110 | 125/145 | 170/195 190* |
Rated power frequency withstand voltage | kV | 28/32 42/48* | 38/45 | 50/60 | 70/80 95* |
Rated frequency | Hz | 50 | |||
Rated continuous current of busbars | A | up to 3150 | up to 2500 | up to 2000 | up to 1250 |
Rated short time withstand current | kA | up to 31,5/3s | up to 25/3s | ||
Rated peak withstand current | kA | up to 80 | up to 63 | ||
Withstand for internal arcing fault | kA | 31,5/1s | 25/1s | ||
Degree of protection | IP 41 / IP 4X | ||||
IAC classification (class of resistance to internal arc) | AFLR | ||||
PM/PI classification (class of partitions) | PM | ||||
LSC classification (class of compartment accessibility) | LSC2B | ||||
Weight of a single switchgear cubicle | kg | 550-1200 | 900-1600 | ||
Busbar system | single | ||||
Overall dimensions (width)** | mm | 600 - 1200 | |||
Overall dimensions (depth)** | mm | 1250 - 2500 | |||
Overall dimensions (height)** | mm | 2150 - 2560 |
* - required according to ГOCT
** - without external guards, covers, doors
Environmental operating conditions
Switchgear ODRA with installed switchgear are adapted for indoor operation under normal conditions, with the following environmental conditions:
Installation altitude above sea level | to 1000 m | |
---|---|---|
Ambient temperature: | peak short-time | +40°C |
maximum average during the day | +35°C | |
maximum average yearly | +20°C | |
minimum sustained | -5°C | |
Air relative humidity at +40°C: | during the start up | max. 80% |
during standstill or operation | max. 95% |